743 articles – 2158 Notices  [english version]
Fiche détaillée Articles dans des revues avec comité de lecture
IEEE Transactions on Power Delivery 24, 4 (2009) 2054 - 2061
Versions disponibles :
Liste des fichiers attachés à ce document : 
PDF
version_editeur.pdf(1.2 MB)
Space vector method for voltage dips and swells analysis
Vanya Ignatova1, Pierre Granjon2, Seddik Bacha3

A new method for voltage dips and swells analysis is presented in this paper. This method is based on the space vector representation in the complex plane and the zero sequence voltage. Indeed, in the case of non-faulted system voltages, the space vector follows a circle in the complex plane with a radius equal to the nominal voltage. It follows the same shape for balanced dips, but with a smaller radius. For unbalanced dips, this shape becomes an ellipse with parameters depending on the phase(s) in drop, dip magnitude and phase angle shift. For swells the space vector shape is not modified, though the zero sequence voltage presents significant changes in its phase and magnitude and can be used for swells analysis. The changes in the space vector and the zero sequence voltage are used to determine the dip/swell time occurrence, to classify and finally characterize the measured power quality disturbance. Algorithms are developed for each step of this automatic voltage dips and swells analysis (segmentation, classification and characterization) and are validated on real measurement data
1 :  Schneider Electric
2 :  GIPSA-lab - Grenoble Images Parole Signal Automatique
3 :  G2ELab - Laboratoire de Génie Electrique de Grenoble
SA-IGA